Power Rating
Emergency Standby Power ESP kVA 887
Emergency Standby Power ESP kW 710
Prime Power PRP kVA 802
Prime Power PRP kW 642
PRP Rating available only with engine supplement: DPA
Voltage V 400/230
Frequency Hz 50
Power factor cos ϕ 0.8
Phase 3
Fuel Diesel
Company with quality certification ISO 9001
Engine specifications
Engine Brand MTU
Model 12V2000G26F
3E
PRP Rating only with supplement: DPA
Operating Speed-Nominal rpm 1500
Engine cooling system Water
[50Hz] Exhaust emission level Unregulated
Nr. of cylinder and disposition 12 V angle
Displacement cm³ 26800
Aspiration Turbocharged
aftercooled
Speed governor Electronic
Maximum gross power LTP ESP kW 780
Prime gross power PRP kW 709
Fan consumption kW 34
Cooling fan air flow rate m³/min 968.4
Oil capacity l 92
Lube oil consumption PRP (max) % 0.8
Coolant capacity l 118
Fuel Diesel
Specific fuel consumption 75% PRP g/kWh 193
Starting system Electric
Starting engine capability kW 9
Electric circuit V 24
For additional information, please check out the PDF supplied by Pramac. GSW880M
Capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours.
WE’RE ALL ENGINEERS HERE…
We only work with a group of tried and trusted suppliers and use the most reliable and effective equipment – which doesn’t always mean the most expensive. And, as controls and systems are continually changing, we keep abreast of all the latest developments to provide you with robust long-term solutions.