Power Rating
Emergency Standby Power ESP kVA 667.4
Emergency Standby Power ESP kW 533.9
Prime power PRP kVA 606.8
Prime power PRP kW 485.4
Voltage V 400/230
Frequency Hz 50
Power factor cos ϕ 0.8
Phases 3
Fuel Diesel
Company with quality certification ISO 9001
Engine specifications
Engine brand Scania
Model DC16 078A
02-41
Operation Speed Nominal rpm 1500
Engine cooling system Water
Exhaust emission level Non Emission
Certified
Nr. of cylinder and disposition 8 V angle
Displacement cm³ 16400
Aspiration Type Turbocharged
Speed governor Electronic
Gross Engine Power ESP kWm 587
Gross Engine Power PRP kWm 536
Fan Power kWm 25
Fan Air flow m³/min 1000
Total Oil capacity l 48
Lube oil consumption PRP (max) % fuel consumption 0.2
Total Coolant capacity l 92
Fuel Diesel
Specific Fuel consumption ESP g/kWh 192
Specific Fuel consumption 75% PRP g/kWh 188
Starting system Electric
Electric circuit V 24
For additional information, please check out the PDF supplied by Pramac. GDW670S/FNE
Capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours.
WE’RE ALL ENGINEERS HERE…
We only work with a group of tried and trusted suppliers and use the most reliable and effective equipment – which doesn’t always mean the most expensive. And, as controls and systems are continually changing, we keep abreast of all the latest developments to provide you with robust long-term solutions.