Power Rating
Emergency Standby Power ESP kVA 2199
Emergency Standby Power ESP kW 1759
Prime Power PRP kVA 2031
Prime Power PRP kW 1625
PRP Rating available only with engine supplement: DPA
Voltage V 400/230
Frequency Hz 50
Power factor cos ϕ 0.8
Phase 3
Fuel Diesel
Engine specifications
Engine Brand MTU
Model 16V4000G74F
3D
PRP Rating only with supplement: DPA
Operating Speed-Nominal rpm 1500
Engine cooling system Water
[50Hz] Exhaust emission level Unregulated
Nr. of cylinder and disposition 16 V
Displacement cm³ 76300
Aspiration Turbocharged
aftercooled
Speed governor Electronic
Maximum gross power LTP ESP kW 1965
Prime gross power PRP kW 1798
Fan consumption kW 55
Cooling fan air flow rate m³/min 2400
Oil capacity l 225
Lube oil consumption PRP (max) % 1
Coolant capacity l 260
Fuel Diesel
Specific fuel consumption 75% PRP g/kWh 191
Starting system Electric
Starting engine capability kW 2 x 7.5
Electric circuit V 24
Radiator
Cooling fan Electric
For additional information, please check out the PDF supplied by Pramac: GSW2275M
Capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours.
WE’RE ALL ENGINEERS HERE…
We only work with a group of tried and trusted suppliers and use the most reliable and effective equipment – which doesn’t always mean the most expensive. And, as controls and systems are continually changing, we keep abreast of all the latest developments to provide you with robust long-term solutions.