Power Rating
Emergency Standby Power ESP kVA 1519
Emergency Standby Power ESP kW 1215
Prime Power PRP kVA 1382
Prime Power PRP kW 1106
Voltage V 400/230
Frequency Hz 50
Power factor cos ϕ 0.8
Phase 3
Fuel Diesel
Engine specifications
Engine Brand Perkins
Model 4012-46TWG3A
Operating Speed-Nominal rpm 1500
Engine cooling system Water
[50Hz] Exhaust emission level Unregulated
Nr. of cylinder and disposition 12 V
Displacement cm³ 45842
Aspiration Turbocharged
Speed governor Electronic
Maximum gross power LTP ESP kW 1314
Prime gross power PRP kW 1200
Fan consumption kW 51
Cooling fan air flow rate m³/min 1320
Oil capacity l 177
Coolant capacity l 196
Fuel Diesel
Specific fuel consumption 75% PRP g/kWh 212
Starting system Electric
Starting engine capability kW 16.4
Electric circuit V 24
For additional information, please check out the PDF supplied by Pramac. GSW1510P
Capable of delivering continuously whilst supplying a variable electrical load when operated for an unlimited number of hours.
WE’RE ALL ENGINEERS HERE…
We only work with a group of tried and trusted suppliers and use the most reliable and effective equipment – which doesn’t always mean the most expensive. And, as controls and systems are continually changing, we keep abreast of all the latest developments to provide you with robust long-term solutions.
Unit 8, Blue Barns Business Park
Old Ipswich Road.
Colchester CO7 7FX
+44 (0)330 1331226
[email protected]